Genset
Model: XP-C1650
Prime
Power: 1500 kVA
Standby
Power: 1650 kVA
Voltage:
380V/400V/415/440V
Frequency:
50Hz
Overall
Dimensions: 5550×2150×2550 mm
Weight:
11000 kg
Engine
Specification
Manufacturer
/ Model CCEC Cummins KTA50-GS8
Air
intake system Turbo, Air/Water cooling
Fuel
system PT type fuel pump, EFC
Cylinder
arrangement 16 in “V”
Displacement 50.3L
Bore
and stroke 159*159(mm)
Compression
ratio 14.9:1
Rated
speed 1500rpm
Max.
Standby power at rated speed 1429KW/1944HP
Governor
type Electronic
Fuel
consumption @ 100% (Prime Power) Load 204
g/kWh 313 L/h
Fuel
consumption @ 75% (Prime Power) Load 210
g/kWh 243 L/h
Fuel
consumption @ 50% (Prime Power) Load 221
g/kWh 175 L/h
Alternator
Specification (Stamford S7L1D-C4)
Number
of Phase 3
Connecting
Type 3 Phase and 4 Wires, Y type
connecting
Number
of Bearing 1
Power
Factor 0.8
Protection
Class IP23
Altitude ≤1000m
Exciter
Type Brushless exciting
Insulation
Class/Temperature Rise H/H
Telephone
Influence Factor (TIF) <50
THF <2%